5:TROUBLESHOOTING

Use the table below to solve minor installation and operation problems. Refer to the APC web site, www.apc.com, for assistance with complex UPS problems.

PROBLEM AND POSSIBLE

 

SOLUTION

CAUSE

 

 

UPS WILL NOT TURN ON

 

 

Batteries are not connected

Check that the battery connectors are fully engaged.

properly.

 

 

button not pushed.

Press the

button once to power the UPS and the connected equipment.

UPS not connected to utility

Check that the power cable from the UPS to the utility power supply is securely

power supply.

connected at both ends.

Very low or no utility voltage.

Check the utility power supply to ensure proper voltage at the receptacle.

 

 

 

UPS WILL NOT TURN OFF

 

 

button not pushed.

Press the

button once to turn the UPS off.

Internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced

 

immediately.

 

 

 

 

UPS BEEPS OCCASIONALLY

 

 

Normal UPS operation when

None. The UPS is protecting the connected equipment.

running on battery.

 

 

 

 

UPS DOES NOT PROVIDE EXPECTED BACKUP TIME

The UPS battery module(s) are

Charge the battery module(s). Modules require recharging after extended outages

weak due to a recent outage or

and wear faster when put into service often or when operated at elevated

are near the end of service life.

temperatures. If the battery module(s) are near the end of service life, consider

 

replacing, even if the Replace Battery LED is not illuminated.

 

 

 

FRONT PANEL LEDS FLASH SEQUENTIALLY

 

The UPS has been shut down

None. The UPS will restart automatically when utility power returns.

remotely through software or an

 

 

optional accessory card.

 

 

 

 

ALL LEDS ARE OFF AND THE UPS IS CONNECTED TO UTILITY POWER

The UPS is shut down and the

None. The UPS will return to normal operation when the power is restored and

battery is discharged from an

the battery has a sufficient charge.

extended outage.

 

 

 

 

BYPASS AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE

The UPS is overloaded.

The connected equipment exceeds the specified “maximum load” as defined in

 

Specifications on the APC web site, www.apc.com.

 

The alarm remains on until the overload is removed. Disconnect nonessential

 

equipment from the UPS to eliminate the overload condition.

 

 

 