2-3
4. Slide the unit into the rack so that the cleats mounted on the side of the unit fit
within the track of the rack-mount rails. If the ears were mounted, screw the
mounted ears into the rack to lock unit into position. (See the installation sheet
located in the box marked, “Accessories.”)
Note:Avoid placing other components directly on top of or behind the unit.
Leave at least one inch of space on all sides to allow for proper air
ventilation. Do not block the fan.
Inserting and Connecting the Battery
In accordance with APC’s interpretation of Department of Transportation
regulations, APC ships this device with the internal battery pack disconnected. The
front bezel of the unit is also not attached to the unit when shipped.
This procedure provides for connection of the battery when the front bezel has been
prematurely installed onto the chassis. Connect the internal battery pack as follows:
1. Grasp the front panel at the sides (Figure 4), and pull the front bezel from the
unit.
Figure 4. Front Bezel Removal