8 Rack Power Distribution Unit AP7610
Rack PDU Configuration

How to configure

through a serial port

connection

1. Connect an available serial port on your computer to the serial port
on the Rack PDU (shown below), using the supplied configuration
cable (940-0144).
2. Run a terminal emulation program such as Windows®
HyperTerminal.
3. Configure the following settings for the serial port:
19,200 bps
–no parity
8 data bits
–1 stop bit
no flow control
4. Press any key on the computer to display the Rack PDU login
screen, which contains the username and password prompts.
5. Log on by using the user name and password for the appropriate
access level:
l
Note
Some terminal emulation programs require that a
device be disconnected and then reconnected for
the new serial port settings to take effect.
Access Level Default
User Name Default Password
Administrator Press
ENTER.Type ap c (in
lowercase).
User Press
ENTER.Press ESC.