 MasterSwitch VM
Menu Items
Outlets
Control actions Outlet Control Actions may be performed on individual outlets (by Individual Outlet Control) or on all accessible outlets as a group (by Master Outlet Control). A Control Action can only be applied to an outlet that is not executing a command. If there is a command pending, the State will be displayed orange.
Item  | Definition | |
  | 
  | |
Immediate On  | Turns outlet on.  | |
  | 
  | |
Immediate Off  | Turns outlet off.  | |
  | 
  | |
  | Turns off the outlet immediately, waits the outlet’s Reboot  | |
Immediate Reboot  | Duration time, and turns the outlet back on. For further  | |
explanation, see the Immediate Reboot sequence diagram on  | ||
  | ||
  | page 4.  | |
  | 
  | |
Delayed On  | Turns on the outlet according to its Power On Delay. For further  | |
explanation, see the Delayed On sequence diagram on page 5.  | ||
  | ||
  | 
  | |
Delayed Off  | Turns off the outlet according to its Power Off Delay. For further  | |
explanation, see the Delayed Off sequence diagram on page 5.  | ||
  | ||
  | 
  | |
  | Immediately powers off all outlets. Each outlet waits the longest  | |
Sequenced  | Reboot Duration time plus its own Power On Delay and then  | |
turns on.  | ||
Reboot†  | ||
Note: The longest Reboot Duration is the longest Reboot  | ||
  | ||
  | Duration (in seconds) in the set of outlets. | |
  | 
  | |
  | Turns an outlet off after the outlet’s Power Off Delay expires.  | |
Delayed Reboot  | Once the outlet’s Reboot Duration expires, the outlet is turned  | |
on. For further explanation, see the Delayed Reboot sequence  | ||
  | ||
  | diagram on page 7.  | |
  | 
  | |
  | Turns off each outlet after its Power Off Delay. Once the outlets  | |
Delayed  | are turned off, each outlet waits the longest Reboot Duration  | |
time plus its own Power On Delay. When this delay expires, the  | ||
Sequenced  | ||
outlet turns on.  | ||
Reboot†  | ||
Note: The longest Reboot Duration is the longest Reboot  | ||
  | ||
  | Duration (in seconds) in the set of outlets.  | |
  | 
  | |
  | Cancel all pending commands for the outlet(s).  | |
Cancel  | Note: Outlet State is displayed in orange with an asterisk (*)  | |
  | when a command is pending for the outlet(s).  | |
  | 
  | 
†Applies only when using Master Outlet Control
Continued on next page
MasterSwitch VM User’s Guide  | 14  |