MasterSwitch VM Users Guide 16

Menu Items
MasterSwitch VM

Unit Configuration

Continued on next page
Item Definition
Name Name of the MasterSwitch VM unit (23 characters
maximum).
ColdStart Delay
ThetimethatMasterSwitchVMwill delay in applying power
tooutlets, once the AC power is applied to the MasterSwitch
VM unit.
OverloadWarning
Threshold
The percentageof a full load that will trigger an overload
warning. Anoverload warning will cause the overcurrent
alarmLED to flash green and sound the audible alarm (if the
overloadaudible alarm property is configured to do so).
OverloadOutlet
Restrictions
Theoverload conditions, if any, that will prevent outlets from
turningon. The following actions are available under this
item:
NoneAlwaysallow outlets tobe turned on.
OnWarningDo not allow outlets to be turned on when the
Overload WarningThreshold has been exceeded.
OnOverloadDo not allow outlets to be turned on when
theloadexceeds100%.
Overload Audible
Alarm
Theoverload conditions, if any, that will cause the audible
alarmto sound. Once the alarm starts sounding, you can
usethe mute button to turn off the alarm or you can clear the
alarm; selecting Disabled will not clear the alarm. The
following actions are availableunder t his item:
DisabledDisablesthe audiblealarm.
OnOverloadSounds the audible alarm when the load
exceeds100 %.
OnOverload WarningSounds the audible alarm when the
load exceedsthe Overload Warning Threshold.
Note: When youchange settings, the new setting is not
used until the nexttime the event occurs. For
example, ifthe overload warning Threshold has
beenexceeded and the setting is then changed from
On Overload to On Warning,the audible alarm will
not be activated.
Low Current
Threshold
Thethreshold for load current below which an SNMP trap is
generated..
RebootDuration
Longestreboot duration in the set of accessible outlets. You
canchange this value only by modifying the reboot duration
ofaccessible outlets. Used b ySequenced Reboot and
DelayedSequenced Reboot.