PROBLEM | CHECK THIS | POSSIBLE CAUSE | CORRECTIVE ACTION |
Pump does not start | Electrical power supply | Controller plug disconnected | Reconnect control plug to |
|
|
| power outlet |
|
| Blown fuse or breaker tripped | Determine cause and replace |
|
| on overload | fuse or reset breaker |
| Pump | Motor failure | Replace pump |
| Sensors | Defective sensors, sensor | Check wiring continuity. |
|
| error | Repair or replace |
Pump starts, but cycles | Differential controller | On and/or off temperature | Reset on and off |
continuously |
| differential set points too low | differentials according to |
|
|
| recommendations |
| Piping | Reversed connections to | Compare with system |
|
| collectors | schematic and reconnect |
|
|
| properly |
| Sensors | Improper location | Compare with system |
|
|
| schematic and reconnect |
|
|
| properly |
Pump cycles after dark | Differential controller | Recooling function active | Controller operating properly. |
|
| and max temperature setting | No fault. |
|
| exceeded |
|
| Sensors | Defective sensors, sensor | Check wiring continuity. |
|
| error | Repair or replace |
Pump runs continuously | Differential controller | Off temperature differential set | Reset off differential according |
|
| too low | to recommendation |
|
| Controller set to “on” position | Set system operation to |
|
|
| “Auto” |
Pump operated but no fluid | Airstop | System | Purge air from airstop in solar |
flows from collectors |
|
| pump station by opening valve |
|
|
| slowly. Caution: after air is |
|
|
| evacuated fluid will flow out |
|
|
| in a small stream and may be |
|
|
| hot. Cover port with a rag to |
|
|
| catch any fluid. |
| Air vent | System | Open air vent on the top of the |
|
|
| system and purge excess air. |
|
|
| Close after purging. |
| Fluid | Loss of fluid from system | Locate leak and repair |
| Isolation valves | Valves in closed position | Open valves |
| Piping | Clogged or damaged piping | Unblock piping or repair |
|
|
| damaged piping |
| Pump | Broken impeller shaft | Replace shaft |
|
| Not vented properly | Install in correct orientation |
|
| Undersized | System piping run too long. |
|
|
| Refer to maximum piping |
|
|
| lengths and adjust |
Noisy system | Air vents | Air trapped in system | Open automatic air vent and |
|
|
| purge airstop in solar pump |
|
|
| station by opening the valve |
|
|
| slowly. Caution: after air is |
|
|
| evacuated fluid will flow out |
|
|
| in a small stream and may be |
|
|
| hot. Cover port with a rag to |
|
|
| catch any fluid. |
| Pump | Bearings are dry or have | Lubricate or replace |
|
| excessive wear |
|
|
| Impeller loose | Tighten or replace impeller |
33