STARTUP / SYSTEM SETTINGS
The AC power cord should be plugged in to an appropriate 115V outlet. The controller will enter an initialization phase in which the operating control lamp will flash red and green. After the initialization period the controller will be in automatic operation with the default settings active.
The
The controller is now ready for operation. The following system settings should be made as indicated. The operational system channels are listed in order of appearance by pressing the forward (1) button.
COL:
Collector Temperature Display range:
TST:
Tank temperature
Display range:
S3, S4:
Additional sensor temperature Display range
TRF:
Temperature return flow Display range
hP:
Operating hours counter Display channel
Shows the current collector temperature.
Shows the current tank temperature (from tank bottom sensor).
Shows the current temperature of the corresponding optional sensor (without control function).
S3 and S4 are only indicated if the temperature sensors are connected.
Shows the current temperature of the optional temperature return flow sensor (S4) when the heat quantity measurement option is activated.
The operating hours counter adds up the solar operating hours of the pump. Full hours are shown on the display.
The total operating hours can be reset. When the operating
hours channel is selected the symbol is permanently shown in the display. The set button (3) must be pressed for approximately 2 seconds in order to go into the reset mode
for the counter. The display symbol will be flashing and the operating hours will be set to 0. In order to finish the reset procedure the set button (3) must be pressed in order to confirm.
In order to interrupt the reset procedure no button should be pressed for about 5 seconds. The controller will automatically return to the indication mode with the previous total.
Once the final display channel is reached the remaining system setting channels may only be accessed by holding the forward
(2) button down for approximately 2 seconds. The following setting channels will then be shown:
ARR:
System arrangement setting
DTO:
2.0to 40.0 °F Default setting 12.0
Recommended setting: 10.0
Shows the current system configuration setting. Arrangement 1 should be used for the system in this package and this setting should not be changed.
Primarily the controller works in the same way as a standard differential controller. If the
27