SYSTEM COMPONENT PART

SYSTEM COMPONENT PART

TABLE 1:

Item

Component

Function

1

Solar collector

Absorbs the sun’s heat energy and transfers this to the heat transfer

 

 

fluid circulating through the collector

2

Solar storage tank

Stores potable water heated by solar generated heat or installed

 

 

back-up electric resistance element

3

Heat exchanger (Not Shown)

Transfers the heat from the collector loop to the potable water in the

 

 

solar storage tank

4

Expansion tank

Allows for the expansion and contraction of the heat transfer fluid as

 

 

it heat and cools.

5

Temperature and Pressure relief

Required by plumbing code to automatically open and dump water if

 

valve

the storage tank exceeds 150 PSI of pressure or 210° F in tempera-

 

 

ture

6

Air vent

Purges air from the collector loop fluid during the installation and is

 

 

shut off later on to prevent glycol losses in steam phase.

7

Drain valve

Used to drain the heat transfer fluid from the collector loop

8

Mixing valve

Used to temper hot water from the solar storage tank with cold inlet

 

 

water to maintain appropriate temperature hot water delivered from

 

 

the system

9

Solar pump station

Controls the flow of heat transfer fluid from the collectors to the tank/

 

 

heat exchanger. For a detailed description of the solar pump station

 

 

see page 20.

10

Temperature sensor

Tank and collector sensor work together to turn the circulating

 

 

pump(s) on and off at preset temperature differentials

 

 

 

STORAGE TANK INSTALLATION

 

 

 

Never operate the electrical heating element without being certain the solar water heater is completely filled with water. If any air is left in the top of the tank, the heating element will burn out.

LOCAL CODES

The installation of this solar water heater must be in accordance with these instructions and all applicable local codes and electric utility requirements. In the absence of local codes, install in accordance with the latest edition of the National Electrical Code (NFPA-70).

TEMPERATURE-PRESSURE RELIEF VALVE

For protection against excessive pressures and temperatures in this water heater, install temperature-pressure protective equipment required by local codes, but not less than a combination temperature-pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves for Hot Water Supply Systems, the latest edition of ANSI Z21.22. This valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 lbs./sq. in.).

Install the temperature-pressure relief valve directly into the fitting of the water heater. Position the valve downward and provide a discharge pipe that must terminate a maximum of six inches above a floor drain or external to the building.

In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 15 feet, or use of more than two elbows can cause restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the temperature-pressure relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6” air gap is provided. To prevent bodily injury, hazard to life or damage to property, the temperature-pressure relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the temperature-pressure relief valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Must terminate a maximum of six inches above a floor drain

7

Page 7
Image 7
American Water Heater 318281-000 instruction manual System Component Part, Storage Tank Installation, Function, Local Codes