TROUBLESHOOTING
PROBLEM | CHECK THIS | POSSIBLE CAUSE | CORRECTIVE ACTION |
No hot water | Storage water heater | No power to auxiliary | Check high temperature |
|
| heating element | protection and push reset |
|
|
| button on the heater |
|
|
| thermostat. (Use caution when |
|
|
| dealing with electricity.) |
| Storage water heater | Thermostat defective | Replace |
| thermostat |
|
|
| Thermostatic mixing valve | Improper adjustment | Check water temperature at |
|
|
| house faucet and adjust valve |
|
|
| setting |
|
| Valve defective | Replace. System must not |
|
|
| be run without thermostatic |
|
|
| mixing valve due to scald risk. |
Not enough hot water | Storage water heater | Undersized for hot water | Replace |
|
| demand load |
|
|
| Thermostat set too low | Increase set point temperature |
|
| Element failure | Replace element |
|
| Thermostat failure | Replace thermostat |
|
| Element disconnected | Reconnect element and set |
|
|
| thermostat to 120°F |
| Check valve | Heat loss due to defective | Inspect valve and repair or |
|
| check valve in solar pump | replace |
|
| station |
|
| Cold water supply dip tube | Missing or defective | Replace dip tube |
| Collectors | Absorber coating degredation | Replace collector |
|
| Collector panel area | Increase collector area |
|
| undersized |
|
|
| Excessive condensation | Inspect and clean weep holes |
|
|
| and vents at bottom. |
|
| Glazing dirty | Clean as required |
|
| Leaks | Repair |
|
| Orientation | Check orientation. Face |
|
|
| collector within 45° of due |
|
|
| South |
|
| Shaded by tree(s) or other | Remove obstacle and shading |
|
| obstructions | or relocate collectors |
|
| Improper tilt | Check tilt for geographic area. |
|
|
| Ensure tilt is equal to latitude |
|
|
| plus 15° |
|
| Improperly plumbed | Compare with system |
|
|
| schematic and correct. |
| Differential Controller | Improper operation (cycling, | Check sensor placement |
|
| late turn on) | and insulation from ambient |
|
|
| conditions |
|
| Faulty sensor | Sensor line break. Check the |
|
| is shown and control | line and repair or replace |
|
|
| |
|
| reads 888.8 instead of |
|
|
| temperature |
|
|
| Faulty sensor | Short circuit. Check the line |
|
| is shown and control | for breaks, metal contact, |
|
| water exposure and corrosion. | |
|
| reads | |
|
|
| |
|
| temperature |
|
|
|
|
|
31