PROBLEM | CHECK THIS | POSSIBLE CAUSE | CORRECTIVE ACTION |
Not enough hot water (cont.) | Differential Controller | Improper wiring or loose | Compare with system |
|
| connections) | schematic. Check for proper |
|
|
| connections. Seal all splices |
|
|
| against moisture |
| Isolation valves | Closed | Open |
| Thermostatic mixing valve | Improper adjustment | Check water temperature at |
|
|
| house faucet and adjust valve |
|
|
| setting |
|
| Valve defective | Replace. System must not |
|
|
| be run without thermostatic |
|
|
| mixing valve due to scald risk. |
| Piping | Insufficient Insulation | Add insulation where required |
|
| High heat losses | Check insulation for splits, |
|
|
| deterioration, absence |
|
| Nighttime thermosyphoning | Check for pump operation at |
|
|
| night |
|
| Improperly plumbed | Compare with system |
|
|
| schematic. Check flow |
|
|
| direction |
|
| Flow blockage | Flush system. Check effluent |
|
|
| for debris. |
|
| Low system pressure | Check pressure gauge. Set |
|
|
| system pressure to correct |
|
|
| setting, check for leaks. |
| Pump | No power | Check breaker, pump cord, |
|
|
| and controller fuse. Repair or |
|
|
| replace |
|
| Flow rated too high or too low | Adjust flow rate |
|
| Faulty pump | Listen for irregular noises |
|
|
| in pump operation. Feel |
|
|
| collector feed and return line |
|
|
| for temperature difference. |
|
|
| Ensure all air is purged from |
|
|
| system. |
|
| Runs continuously | Check sensors for shorts |
No hot water in the morning | Storage water heater | Circuit breaker shut off | Turn breaker on |
| Differential controller | Sensor wires reversed | Ensure the collector and |
|
|
| tanks sensors are wired to |
|
|
| the correct position on the |
|
|
| controller |
Water too hot | Thermostatic mixing valve | Improper adjustment | Check water temperature at |
|
|
| house faucet and adjust valve |
|
|
| setting |
|
| Valve defective | Replace. System must not |
|
|
| be run without thermostatic |
|
|
| mixing valve due to scald risk. |
No water | Valve closed | Open valve | |
Pump does not start | Differential controller | Controller set to “off” position | Set system operation to |
|
|
| “Auto” |
|
| Uplugged | Return power to controller |
|
| On and/or off temperature | Reset on and off |
|
| differential set points too high | differentials according to |
|
|
| recommendations |
|
| Loose contacts | Clean contacts and tighten |
|
|
| connections or replace |
|
| Blown fuse | Replace fuse |