Chimney Connection

Important: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces.

!

The connector must be installed above the extreme

 

bottom of the chimney to prevent potential

 

stoppage of the flue gases.

!

The connector must be firmly attached and sealed

 

 

to prevent it from falling out.

!

To aid in removing the connector, a thimble or slip

 

 

joint may be used.

!

The connector must not extend beyond the inner

 

 

edge of the chimney as it may restrict the space

 

between it and the opposite wall of the chimney

Figure 10

Certified Lined

Chimney Termination

Chimney

Vent System

 

 

2 ft. min. above any object

 

within 10 ft.

3 ft. min.

Horizontally

 

Maintain

 

clearance

Seal

 

 

Do not extend

 

vent beyond edge

 

of chimney

Slope up

 

1/4 in.

 

per

Vent

ft. min.

Connector

(Figure 10).

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s drafthood by a certified vent connector or by directly originating at the drafthood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Figure 11

Vertical Gas

Vent System

With Type B

Double Wall

Vent Pipe

Maintain clearance

 

Listed Vent Cap

3 ft. min.

2 ft. min. above any object

within 10 ft.

 

horizontally

 

Type B Double

 

Wall Vent Pipe

 

Maintain

Vent

specified

clearance

connector

slope up

 

1/4 in. per

 

ft. min.

 

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials (Figures 11 and 12).

Important: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 12).

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys.

Figures 10-12 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-latest edition and the guidelines set forth by prevailing local codes.

Figure 12

 

Listed Vent Cap

Venting Through

5 inches min.

Maintain

a Chimney

with Type B

 

specified

 

clearance

Doublewall

 

Vent Pipe.

 

 

Maintain

 

 

clearance

Seal

 

 

 

 

 

Vent

 

Slope up

Connector

 

 

 

1/4 in.

Unused chimney

 

per

 

ft. min.

flue or masonry

 

 

enclosure

11

Page 11
Image 11
American Water Heater 6510319 installation instructions Chimney Connection, Vertical Exhaust Gas Vent