Troubleshooting
The Guardian CP™ incorporates
PROBLEM | CAUSE | SOLUTION | |||
|
|
|
|
| |
| 1. | No Power. | 1. | Check circuit breaker and fuses, tighten connections. | |
| 2. | Faulty wiring. | 2. | Check wiring per installation diagram in this booklet. If pump hums, | |
Pump will not start. |
|
|
| but will not start, check pump motor wiring (115/230V). | |
3. | Damaged motor. | 3. | If display illuminates with no error code, but pump will not start, | ||
| |||||
|
|
|
| replace pump. | |
| 4. | Damaged control. | 4. | If power is present at L1/L2 but display is blank, replace control. | |
|
|
|
|
| |
| 1. | Supply closed/blocked. | 1. | Open all supply valves, ensure check valve is not sticking, clean | |
|
|
|
| any filters. | |
Pump runs but will | 2. | Bypass loop open. | 2. | Close bypass valve. | |
|
|
|
| ||
not build pressure. | 3. Pump plumbed backwards. | 3. | Reverse inlet/outlet. | ||
| 4. | Bad internal parts. | 4. | Check for bad seals or broken impeller. Repair or replace as | |
|
|
|
| necessary. | |
|
|
|
| ||
Pump builds | 1. Operating pressure set too high. | 1. | Reduce control setting as necessary. | ||
2. | Bad internal parts. | 2. | Check for bad seals or broken impeller. Repair or replace as | ||
pressure but will not | |||||
|
|
| necessary. | ||
shut off. |
|
|
| ||
3. | Control line blocked. | 3. | Remove control line and blow compressed air to clear. | ||
| |||||
|
|
|
|
| |
Pump starts too often | 1. | Control differential too narrow. | 1. | Set | |
2. Tank precharge incorrect. | 2. | Set air pressure 2 psi below | |||
(cycles under 30 |
|
|
| pressure is zero. | |
sec.). |
|
|
| ||
3. | Waterlogged pressure tank. | 3. | If water emerges from tank air stem when depressed, replace tank. | ||
| |||||
|
|
|
|
|
To reset control at any time, press buttons simultaneously for 5 seconds.
To "invert" the display for easier viewing, press together for 3 seconds.
CODE | REASON | ACTION | CAUSE & REMEDY | ||
|
|
|
| ||
E1 | Rapid cycle | Switch continues to operate. | See “Pump Starts Too Often” above. | ||
Excessive amp draw | Have pump checked for proper operation. | ||||
|
| ||||
|
|
|
|
| |
E2 | Shuts off pump. Auto restart | 1. | Determine cause of | ||
| (running pressure) | after 60 min. | 2. | Check Wiring. | |
| below 10 PSI |
| 3. | Inspect pump. | |
|
|
|
| ||
E3 | Improper voltage | Shuts off pump. | Restore voltage to proper range. Pump automatically | ||
|
|
| restarts with proper voltage. | ||
|
|
|
|
|
THE GUARDIAN CP CONTROL CONTAINS NO SERVICEABLE PARTS. REMOVAL OF MAIN CIRCUIT BOARD COVER WILL VOID WARRANTY.