Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower10
Customize the Main and Switched Outlet Groups

Use the Configuration menus to change the Main Outlet Group and the Switched Outlet Group settings.

Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set at the factory.
These settings can only be modified using an external interface, such as the NMC Web interface.
NMC IP Address Mode
NMC IP Address
NMC Subnet Mask
NMC Default Gateway
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec Set the value in
seconds The amount of time the UPS or a Switched Outlet
Group will wait between receiving the command to
turn on and the actual startup.
Turn Off Delay 0 sec (UPS Outlets)
90 sec (Switched
Outlet Groups)
Set the value in
seconds The amount of time the UPS or a Switched Outlet
Group will wait between receiving the command to
turn off and the actual shut down.
Reboot Duration 8 sec Set the value in
seconds The amount of time the UPS or a Switched Outlet
Group must remain off before it will restart.
Minimum Return
Time
0 sec Set the value in
seconds The amount of battery runtime that must be available
before the UPS or a Switched Outlet Group will turn
on after a shutdown.
Load Shed On
Battery
Disabled •Enable
•Disable When the unit switches to battery power, the UPS
will disconnect power to the Switched Outlet Group
to save battery runtime.
Configure this delay time, use the LOAD SHED TIME
WHEN ON BATTERY setting.
Load Shed Time
when On Battery
1800 sec Set the value in
seconds The amount of time the outlets will function on
battery power before they will turn off.
Load Shed On
Runtime
Disabled •Enable
•Disable When the battery runtime falls below the specified
value, the Switched Outlet Group will turn off.
Configure this time using the LOAD SHED RUNTIME
REMAINING setting.
Load Shed On
Runtime
Remaining
120 sec Set the value in
seconds When the remaining runtime reaches this level, the
Switched Outlet Group will turn off.
Load Shed on
Overload
Disabled •Disabled
•Enabled In the event of an overload (greater than 107%
output), the Switched Outlet Group will immediately
turn off to conserve power for critical loads. The
Switched Outlet Group will only turn on again with
a manual command.