7Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower
Configuration

UPS Settings

Start-up Settings

Configure these settings at initial start-up, using the display interface. As an alternative, configuration
can be performed using APC PowerChute® software.
Note: During start-up, use the display interface to configure these settings. If nothing is
selected, the unit will use the default settings.

General Settings

Configure these settings at any time. Use the display interface or APC PowerChute® software.
Function Factory Default Options Description
Language English • English
•French*
•German*
• Spanish*
•Italian*
• Portuguese*
• Japanese*
The language for the display interface.
*Language options will vary by model.
Local Power
Quality Good • Good
•Fair
• Poor
Select the quality of input utility power.
If Good is selected, the unit will go on battery power
more often to provide the cleanest power supply to the
connected equipment.
If Poor is selected, the UPS will tolerate more
fluctuations in power and will go on battery power less
often.
If unsure of the local power quality, select Good.
Menu Type Standard Standard or
Advanced The Standard menus display a limited set of menus
and options. The advanced menus include all
parameters.
Function Factory Default Options Description
High Transfer Point 100 Vac:
108 Vac
108 Vac - 114 Vac To avoid unnecessary battery usage, set the transfer
point higher if the utility voltage is chronically high and
the connected equipment is known to work under this
condition. The Power Quality setting will
automatically change this setting.
Note: Use the Advanced Menus to configure this
setting.
120 Vac:
127 Vac
127 Vac - 136 Vac
230 Vac:
253 Vac
253 Vac - 265 Vac