Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 63
Image 63
No or low flow with a

MECHANICAL

CONDITIONS

CONTD

Alarm

Possible cause

Solution

Low Suction Pressure (pump is running and com- pressor is off)

No or low flow with a

Check To Process and From

failed flow switch and

Process valves to see if they

RTD.

are open.

 

Check Flow switch and

 

RTD. Replace as needed.

 

 

Compressor suction valve

Open valve.

is closed.

 

 

 

No load on the Chiller.

Check process load for

 

required load. Chiller may be

 

oversized.

 

 

The Evaporator is fouled.

Clean Evaporator. See

 

Cleaning the Evaporator or

 

Water-cooled Condenser, in the

 

Maintenance section.

 

 

The Evaporator is frozen.

Check RTD; Replace as

 

needed.

 

Check minimum allowable

 

setpoint for percent glycol

 

used.

 

 

There is a refrigerant

Check for oil in chiller cabinet

leak.

and bubbles in refrigerant site

 

glass. Consult Conair Service

 

for repair.

 

 

The pressure switch is

See Checking Pressure

Switches, in the

faulty.

Troubleshooting section.

UGH016/0500

Series 1 Portable Chillers, TIC Control TROUBLESHOOTING 6-13

Page 63
Image 63
Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control Mechanical Conditions, Alarm