CONTROL PROBLEMS

Look here if the control panel is not lit, or if the power is on and the Portable Chiller will not run.

CONTROL PROBLEMS

Symptom

Possible cause

Solution

The control is not lit and the chiller is not working.

Power is not reaching the chiller.

Check the power cord and plug. Make sure the cord and plug are properly connected.

Make sure the main discon- nect switch is on.

Check fuses and breakers. Replace or reset as required.

The correct power is not
Check the voltage specification
reaching the unit
on the chiller nameplate.

 

 

There is a problem with the TIC control.

Check fuses and replace as needed.

Check the power to the tem- perature controller. Reconnect or replace as needed.

Check the TIC indicator lights and replace as needed.

There is a problem with the control panel.

The control panel may have failed. Contact Conair Service.

UGH016/0500

Series 1 Portable Chillers, TIC Control

TROUBLESHOOTING 6-5