Conair UGH016/0500 manual Control Problems, Symptom, Possible cause, Solution, Cont’D

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 56
Image 56
Solution

CONTROL

PROBLEMS

CONTD

Symptom

Possible cause

Solution

 

 

 

The control is lit and there is no alarm condition. The com- pressor hums, but does not run.

The input voltage is incorrect

There is a phase loss.

Check the main supply volt- age. It must be within 10% of the nameplate rating.

Check the fuses on the main power supply.

Check the phase-to-phase voltages.

Check phase continuity

through the compressor con- tactor.

Check the wiring at the compressor.

Replace or repair as needed.