Conair UGH016/0500 Answering An Alarm, Pump, Compressor, Alarm Condition, Description, Status

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 54
Image 54
ANSWERING AN ALARM

ANSWERING AN ALARM

When an alarm condition occurs, the alarm light on the con- trol panel lights. It stays lit until the alarm condition is cor- rected. If you have the optional audible alarm, pressing the Enter button silences the audible alarm.

To find out what is causing the alarm, check the indicator lights on the control panel for the pump and compressor sta- tus. If the pump and compressor are both off, check the water tank level, flow valves, and the pump. If the pump is on and the compressor is off, check the compressor, suction pressure and discharge pressure.

 

 

Pump

Compressor

Alarm Condition

Description

Status

Status

 

 

 

 

Low Water Tank Level

The water level in the pump tank is low.

OFF

OFF

Flow Fault

There is no flow of the process fluid at the

OFF

OFF

 

pump discharge.

 

 

Pump Overload

There is a high amperage condition; the

OFF

OFF

 

pump is drawing too much current.

 

 

Compressor Overload

There is a high amperage condition; the

ON

OFF

 

compressor is drawing too much current.

 

 

High Discharge Pressure

The refrigerant pressure, as measured at the

ON

OFF

 

compressor outlet is high.

 

 

Low Suction Pressure

The refrigerant pressure, as measured at the

ON

OFF

 

inlet of the compressor is low.

 

 

 

 

 

 

Refer to the Troubleshooting tables and the wiring diagrams to correct the alarm condition.

6-4

TROUBLESHOOTING Series 1 Portable Chillers, TIC Control

UGH016/0500

Page 54
Image 54
Conair UGH016/0500 manual Answering An Alarm, Pump, Compressor, Alarm Condition, Description, Status