FILLING THE CHILLER

FILLING THE CHILLER

The Chiller is shipped without coolant. The chiller is filled manually during installation. Use water as the coolant down to 40 °F (4 °C). Below 40 °F and down to 20 °F (-7 °C), use an ethylene glycol or propylene glycol solution.

To fill with water:

1

Attach water hose to Fill/Drain valve.

 

 

2

Close the To Process and From Process valves.

 

 

3

Open the Fill/Drain valve and fill chiller

 

to the fill mark on the Water Level sight glass. If the

 

chiller is overfilled, the excess water spills out the vent

 

tube. DO NOT OVERFILL.

4

Close the Fill/Drain valve.

 

 

5

Disconnect water hose from Fill/Drain valve.

Water Level sight glass

From Process valve

To Process valve

Fill/Drain valve

To fill with glycol solution:

1

Mix the glycol to the proper percentage.

Use the table to determine the percentage (by volume) of glycol needed for the process temperature (in °F) you require. Do not choose a temperature below 15 °F (-9 °C). Mix the proper percentage of glycol with water.

WARNING: Refrigerant hazard

Only certified refrigerant technicians should examine and correct problems involving the refrigerant circuit.

3-6

INSTALLATION

Series 1 Portable Chillers, TIC Control

UGH016/0500