Conair UGH016/0500 manual Checking Pressure Switches, Time, WARNING Coolant hazard

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 72
Image 72
CHECKING

CHECKING

PRESSURE

SWITCHES

WARNING: Coolant hazard

Coolant can cause freezing of skin. All proper precautions should be taken any time the cool- ing system is worked on. Any adjustment that involves the coolant should only be performed by a certified refrigeration technician.

The pressure switch is a non-adjustable switch. To check the pressure switch:

1

Locate the pressure switch.

Always refer to the wiring dia- grams you received with your chiller to locate specific elec- trical components.

 

Use the wiring diagrams that came with your chiller for

 

exact location. Location varies depending on size of unit.

 

 

2

Check the connections.

 

Make sure all connections to the switch are secure.

 

Tighten as needed.

 

 

3

Check the control signal in the electrical panel.

 

Refer to the wiring diagram and the following table for

 

the switch status:

Inputs

Outputs

I

1

2

3

4

5

6

7

 

8

9

10 11 12

 

 

 

DAY

 

 

 

 

 

 

 

 

 

 

 

TIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

1

2

3

 

4

5

6

7

8

In this example, inputs 7 and 8 are highlighted; they are in normal position. If they are not highlighted the input is out of range.

 

Input

Description

Output

Description

 

1

Chiller Stop

1

Compressor Starter

 

2

Chiller Start

 

2

Compressor Run Lamp

 

3

Level Switch

 

3

Pump Starter

 

4

Flow Switch

 

4

Pump Run Lamp

 

5

Compressor Running

 

5

Alarm Lamp

 

6

Pump Running

 

6

Optional Auto-Fill Solenoid

 

7

Suction Pressure Switch

 

7

Optional Alarm Bell

 

8

Discharge Pressure Switch

 

8

Optional Alarm Strobe

 

9

Low Temperature Deviation

 

 

 

 

10

Optional Auto-Fill Level Switch

 

 

 

11

Pressure Differential Switch

 

 

 

 

(7.5, 10, 15 ton only)

 

 

 

12

Optional Alarm Silence

 

 

 

 

 

 

 

 

 

 

 

 

6-22TROUBLESHOOTING Series 1 Portable Chillers, TIC Control

UGH016/0500

Page 72
Image 72
Conair UGH016/0500 manual Checking Pressure Switches, Time, WARNING Coolant hazard, Locate the pressure switch