Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 81
Image 81
CONTROL SETTINGS

Use this table when configuring the temperature controller. Refer to the manufacturer’s manual that accompanies this User Guide for detailed information.

When the control displays the text listed in the Display col- umn, you can scroll to, and change, the settings listed in the Parameter column.

CONTROL SETTINGS

Display

Parameter

Description

Setting

Units

InP

SP.LL

Lower Setpoint limit

40

°F

 

SP.HL

Upper Setpoint Limit

70

°F

 

TyPE

Input sensor type

rtd

100 ohm rtd

DSPL

dspl

Display menu

----

-----

 

Unit

Temperature units

F

°F or °C

 

 

 

 

 

OutP

O1.ty

Output 1 Type

PID

-----

 

O1.ac

Output 1 action

re

Reverse action

 

O1.cy

Output 1 cycle type

5

Seconds

 

O1.hl

Output 1 High limit

80%

% time HGV is on

 

O2.ty

Output 2 Control Type

ALr

-----

 

O2.aa

Output 2 Alarm 1 Action

nor

-----

 

O2.ao

Output 2 process

DE.L

Alarm set to low deviation

 

O2.ih

Output 2 alarm inhibit

En

Enabled

 

O2.SP

Output 2 alarm setpoint

4

°F Low deviation

Cnrl

Pb1

Proportional Band-gain

1

-----

 

der

Derivative Action - rate

0

-----

 

OFFS

Manual reset

OFF

-----

 

Int

Integral Action - reset

0

-----

 

 

 

 

 

UGH016/0601

Series 1 Portable Chillers, TIC Control

APPENDIX D-1

Page 81
Image 81