Compressor discharge

MECHANICAL

CONDITIONS

CONTD

Alarm

Possible cause

Solution

High Discharge

Compressor discharge

Pressure, cont’d

valve closed.

Overcharged with refrig- erant.
Faulty water regulating valve.
Faulty pressure switch.

Open valve.

See Checking the Refrigerant Charge in the Maintenance section.

Repair or replace the valve.

See Checking the Pressure Switches, in the Troubleshooting section.

6-12TROUBLESHOOTING Series 1 Portable Chillers, TIC Control

UGH016/0500

Page 62