STARTUP SETTINGS

BMC and BMC-6X Installation and Operation Manual

STARTUP SETTINGS

PROGRAM CHANGE SETTINGS ALERT

A good practice after performing any Startup menu modifications is to check all operating settings and adjustments to match the new settings.

PROGRAM CHANGE SETTINGS

To be able to change the BMC settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a lock.

STARTUP SEQUENCE

Button: MENU/<System Startup>

When powered, the BMC performs a self diagnostics-test on its components.

On the first power up, the System Startup screen will appear after the initialization is complete. If it doesn’t, the BMC has already been configured.

The System Startup menu sets the main parameters like the type of sensor, the type of output, and the modulating mode.

SENSOR TYPE

Set Point °F, Set Point °C, Reset °F, Reset °CDefault: Set Point °F
Button: MENU/<System Startup>/..../Sensor type

 

Reset mode is only available if an outdoor sensor is connected to terminals 25 and 26. DO NOT select Reset without an outdoor sensor.

The same Weil McLain temperature sensor can display in either °F or °C.

If °F is selected, all temperatures and settings will be displayed in degrees Fahrenheit and the BMC will operate as a Set Point Control in degrees Fahrenheit.

If °C is selected, all temperatures and settings will be displayed in degrees Celsius and the BMC will operate as a Set Point Control in degrees Celsius.

Set point mode does not require an outdoor sensor. If an outdoor sensor is connected in Set Point mode it will be used only as an outdoor cutoff point. That is, to turn the boilers and system pump off.

 

 

PROGRAM

RUN

--------

SYSTEM

STARTUP

------

 

 

 

(START)

 

 

 

to

continue

 

BACK

 

 

 

 

START

----------

SENSOR

TYPE ---------

Set

Point

F

 

 

Set

Point

C

 

 

Reset

F

 

 

 

Reset

C

 

 

 

BACK

 

 

 

SAVE

------STARTUP SEQUENCESENSOR TYPESet Point °F, Set Point °C, Reset °F, Reset °CDefault: Set Point °FButton: MENU/<System Startup>/..../Sensor typeEMS INPUT MODE (AVAILABLE IN SET POINT ONLY)Disable, EnableEMSDefault: Disable4mA Adjustable from 70ºF/21ºC to 200ºF/93ºCDefault: 140ºF/ 60ºC20mA Adjustable from 90ºF/32ºC to 240ºF/116ºCDefault: 200ºF/ 93ºCButton: MENU/<System Startup>/..../EMS Input Mode120FSELECTING THE OUTPUT TYPEINPUT4-20mA, 0-5V, 0-10V, 1-5V, or 2-10V OutputsDefault: 0-10Vselected (0-5V, 0-10V, 1-5V, 2-10V).Manual backgroundManual backgroundManual backgroundMODEManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background-------

DisableManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

EnableManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

EMS INPUT MODE (AVAILABLE IN SET POINT ONLY)

Disable, EnableDefault: Disable
4mA Adjustable from 70ºF/21ºC to 200ºF/93ºCDefault: 140ºF/ 60ºC
20mA Adjustable from 90ºF/32ºC to 240ºF/116ºCDefault: 200ºF/ 93ºC
Button: MENU/<System Startup>/..../EMS Input Mode

 

This allows the BMC to receive an external set point from an EMS/BMS system.

You must select the 4mA (min) and 20 mA (max) Set Points in the following screen.

The 4mA can be set to any temperature between 70ºF to 200ºF.

The 20mA can be set to any temperature between 90ºF to 240ºF. However, the minimum must be 20ºF higher than the 4mA setting.

Connect the 4-20mA EMS Control Interface to the BMC RS485 connection.

BACK

SAVE

------Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundEMSManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background4maManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundSETPOINTManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background------

120Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundFManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

[

]

BACK

SAVE

SELECTING THE OUTPUT TYPE

 

------- OUTPUT

A TYPE --------

 

4-20ma

 

4-20mA, 0-5V, 0-10V, 1-5V, or 2-10V OutputsDefault: 0-10V

0-10v

 

0-5v

 

Button: MENU/<System Startup>/..../Output A type/Output B type

 

 

 

2-10v

 

• Outputs can be configured for 4-20mA operation (current) or the voltage range can be

1-5v

 

selected (0-5V, 0-10V, 1-5V, 2-10V).

 

BACK

SAVE

 

 

 

Check the modulating motor to determine its control requirements.

When using Extension panels, connect them prior to configuring the Output Type. Otherwise, the BMC will not configure them properly.

Select the appropriate Output Type for each of the boilers. The BMC can have a different Output type for each boiler.