SYSTEM SETTINGS

BMC and BMC-6X Installation and Operation Manual

SYSTEM SETTINGS

Button: MENU/<System Settings>

The Settings 1 and Settings 2 menus provide access to adjusting and fine-tuning the system for enhanced comfort and more fuel savings. The BMC behaves differently based on the selected Control Modes (see Startup Settings).

Gain

System Run-On

Lead Rotation

Setback

Purge Delay

Last Stage Hold

Lag Delay

Day/Night Schedules

Standby Time

GAIN ALERT

To be able to change the BMC settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a lock.

GAIN

Adjustable from -10 to +10

Default: 0

Button: MENU/<System Settings>/Gain

 

The Gain adjusts the aggressiveness of the BMC PID logic to control how much modulation is changed when the system temperature is different from the Set Point.

A Gain of 0 is a good starting point for all systems.

If during normal load conditions, the system temperature tends to oscillate significantly, decrease the Gain by two numbers (for example, from 0 to -2). Wait for at least 15 minutes before evaluating how the change has affected the system.

If during normal load conditions the system temperature tends to remain consistently below the Set Point (or consistently above the Set Point), increase the Gain by two numbers (for example, from 0 to 2). Wait for at least 15 minutes before evaluating how the change has affected the system.

LEAD BOILER ROTATION

Adjustable Manual, Time (1 hr to 60 Days), Last-OnDefault: Time (24Hours)
Button: MENU/<System Settings>/Lead Rotation

 

The Lead Boiler is the first boiler brought on when output is required.

The Lead Boiler can be rotated automatically, manually or based on Last-On. The automatic rotation is recommended.

The current Lead Boiler is shown in brackets on the main display.

Only boilers which are set to Auto Mode can be Lead. Therefore, not all the boilers may be available when manually selecting a new Lead Boiler.

PURGE DELAY

Adjustable from 0.0min to 10.0minDefault: 1.0min
Button: MENU/<System Settings>/Purge Delay

 

Many boilers go through a purge cycle before they are brought on line.

When the BMC activates a boiler, it does not start to calculate its output until the Purge Delay is over. This allows the boiler to fully come online and begin producing output.

The Purge Delay helps prevent short cycling of a newly activated burner. Once the burner is activated, it MUST run through the entire Purge Delay period.

The minimum Purge Delay setting MUST be set to the time required by the boiler manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5min will equal 90 seconds.)

The Message Display Line will display Purge Delay and the amount of time remaining in the purge.

----------

SETTINGS

1

----------

Gain

 

 

 

 

 

+0

Lead

Rotation

 

Time

Purge Delay

 

 

0.0min

Lag

Delay

 

 

0min

<More Settings>

 

 

 

BACK

 

 

 

 

SELECT

----------

SETTINGS

2

----------

Standby

Time

 

10min

System

Run-On

 

0min

Setback

 

 

 

0

F

Last

Stage

Hold

 

0

F

Set

Time

 

 

12:03Pm

<Day/Night

Schedules>

 

BACK

 

 

 

 

SELECT

 

 

PROGRAM

 

RUN

----------------

GAIN --------------

 

 

 

 

+0 F

 

 

 

[]

 

 

 

 

 

 

BACK

 

 

 

 

SAVE

 

--------

LEAD ROTATION

-------

 

Manual

 

 

 

 

 

 

Time

 

 

 

 

 

 

Last-On

 

 

 

 

 

BACK

 

 

 

 

SAVE

 

--- AUTO ROTATE PERIOD ---

 

 

 

24hrs

 

 

 

[]

 

 

 

 

 

 

BACK

 

 

 

 

SAVE

 

---- MANUAL LEAD STAGE ----

 

A

 

 

 

 

 

 

B

 

 

 

 

 

 

C

 

 

 

 

 

 

D

 

 

 

 

 

 

E

 

 

 

 

 

 

BACK

 

 

 

 

SAVE

 

---------

PURGE

DELAY

---------

 

 

 

0.0min

 

 

 

[]

 

 

 

 

 

 

BACK

 

 

 

 

SAVE

 

Adjustable from -10 to +10 ALERT

Set Purge Delay as per boiler manufacturer recommendation.

19

Page 19