BMC and
LAG DELAY | Default: 0min | DELAY | |
Adjustable from 0min to 60min |
|
| |
Button: MENU/<System Settings>/Lag Delay |
| 0min | |
• The Lag Delay requires the previous stage to remain at 100% modulation for the full | [] |
| |
period of the Lag Delay before another Stage can be activated. For example, if the Lag |
|
| |
Delay was set to 10 minutes, the Lead Stage would need to remain at 100% modulation | BACK | SAVE | |
for a full ten minutes (never backing down to even 99%) before a lag stage could be |
|
| |
activated. The Message Display Line will display Lag Delay and the remaining time. |
|
|
•Set the Lag Delay to 0 min when two or more Stages will generally be needed to hold the load.
•The Lag Delay is useful in installations where one unit should usually have enough output to hold the load unless it fails or load conditions become extreme.
•The Lag Delay overrides the value of the Modulation Start % selected for each stage. Regardless of that setting, the previous stage must reach 100% and stay there before the lag stage can be activated.
•The full Lag Delay must always elapse regardless of what happens to system temperature. Therefore, set the Lag Delay to 0 min if you want smooth set point control using multiple units.
STANDBY DELAY
Adjustable from 1min to 60min | Default: 10min |
Button: MENU/<System Settings>/<More Settings>/Standby Time | 10min |
• The Standby Delay only applies to boilers in Standby Mode. See Mode on page 25.
•A boiler can be set to be a Standby boiler using the Stage Menu.
• A Standby boiler can only be activated after all the boilers in Auto Mode have run at | BACK | SAVE |
100% modulation for the full Standby Time. |
|
|
•Standby boilers are used for backup or extreme load conditions only. A Standby boiler can never be a Lead Stage
•The full Standby Delay must always elapse regardless of what happens to system temperature. Therefore, shorter Standby Times will result in smoother set point operation in extreme conditions. Longer Standby Times may prevent a Standby boiler from firing if the other boilers can eventually meet the load, or if the load decreases.
SYSTEM RUN-ON
Adjustable from 0min to 360min | Default: 0min |
|
|
Button: MENU/<System Settings>/<More Settings>/System |
|
| 0min |
• The SYS relay will energize whenever the Outdoor temperature (OD) is below the | [] |
| |
Outdoor Cutoff and the Shutdown is Open or the Tstat is closed. When the Outdoor |
|
| |
temperature increases 2°F above the Outdoor Cutoff after the last burner relay has de- | BACK | SAVE | |
energized, the SYS relay will stay on for a period set by the System |
|
|
•A common use for the System
•The System
SETBACK
Adjustable from 0F°/0C° to 75F°/42C° | Default: 0F°/0C° |
Button: MENU/<System Settings>/<More Settings>/Setback |
|
•The Setback feature can be used to provide the BMC with a lower temperature Set Point when less load is required.
•The lower Set Point will appear on the main display indicating this condition.
•For example, if the calculated temperature is 180°F and the Setback is 20°F, then when in Setback, the BMC will hold a Set Point of 160°F.
•A typical use for Setback is to provide less system temperature to a building during the night or on the weekends when building is not occupied, but heat is still required.
•The amount of Setback selected is subtracted from the Set Point when a Setback Input Signal is received or the Night Time schedule setting started.
SETBACK | |
| 0 F |
[] |
|
BACK | SAVE |
20