BMC and BMC-6X Installation and Operation Manual

SPECIFICATIONS

Voltage Input:

.

. . .

 

120 VAC 60 Hz

Power Consumption:

.

. . .

.

. . 12 VA Max

Operating Temperature:

20°F/-7°C to 120°F/49°C

Operating Humidity:

.

. . .

.

.

20% to 80%

Dimensions:

 

11"W x 9" H x 3 ¾" D

Weight:

.

. . .

.

.

2.5 pounds

BMC SPECIFICATIONS

Lead Stage Rotation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time ( 1 to 1440 Hours (60 days)), Manual, Last-On

Pump Output:

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. . . . . . . . . . . . .

.

.

.

(1) N.O. S.P.S.T

Boiler Modes:

. .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.Auto, Manual (0% - 100%), Standby, On, Off

Standby Time:

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. . . . . . . . . . . . .

.

.

. 1 to 60 minutes

Modulating Output Types: . . .

 

Total of four outputs. Can be either Current (4-20mA) or VDC (0-5V, 0-10V, 1-5V, 2-10V)

Output Relay Ratings:

 

(5) 1 Amp inductive (1/8HP), 6Amp resistive at 120 VAC 60 Hz, 15A total for all circuits

Add-On BMC-6X Panels: . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . .up to two BMC-6X Panels using RS485

Ignition Point %:

. .

. .

. .

. .

. .

. .

. .

. .

. .

. .

. .

. .

. . . . . . . . . . . . . .

.

.

. . . .

1 to 50%

Modulation Start Point %: . . .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. . . . . . . . . . . . .

.

.

.

. . .

0 to 100%

Modulation Modes:

. .

. .

. .

. .

. .

. .

. .

. .

. .

. .

. .

. .

. . . . . . . . . . . . . .

.

Normal or Parallel

Temperature Display:

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. . . . . . . . . . . . .

Fahrenheit or Celsius.

Display: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Graphical Alphanumeric (7 rows x 21 char. each)

LED: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (1) System Output relay, (4) Boiler Output relays

Sensor Ranges: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Outdoor temperature sensor -35°F/-37°C to 250°F/121°C Heating system sensor -35°F/-37°C to 250°F/121°C

Outdoor Cutoff Range:

. . . . . . . . . . . .

.

.

. .20°F/-7°C to 100°F/38°C, ON and OFF

Reset Ratio Range:

. . . . . . . . . (1.00

: 4.00) to (4.00 :

1.00) (Outdoor : System Water)

Offset Adjustment:

. . . . . . . . . . . . . .

. .

.

. . . . . .

. -40F°/-22C° to + 40F°/+22C

Minimum Water Temperature:

. . . . . . . . . . . .

.

.

. . . . .

. .

 

 

70°F/21°C to 170°F/77°C

Maximum Water Temperature (Reset Only):

. . . . . . . . . . . .

.

.

. . . . .

.

 

90°F/32°C to 240°F/116°C

Set Point Temperature Range:

. . . . . . . . . . . .

.

.

. . . . .

.

 

70°F/21°C to 250°F/121°C

EMS Temperature Range:

. . . . . . . . . . . .

.

.

. . . . .

.

 

70°F/21°C to 240°F/116°C

Domestic Hot Water:

. . . . . . . . . . . . . .

. .

.

. . . . . . with Priority or without Priority

Pump Run-On:

. . . . . . . . . . . . . .

. .

.

. . . . . .

. .

.

.

. . .

0 to 360

minutes

Purge Delay:

. . . . . . . . . . . . . .

. .

.

. . . . . .

. .

.

.

. .

0.0 to 10.0

minutes

Lag Delay:

. . . . . . . . . . . . . .

. .

.

. . . . . .

. .

.

.

. . .

. 0 to 60

minutes

Last Stage Hold:

. . . . . . . . . . . . . .

. . .

. . . . . .

. . . . . . 0F°/0°C to 30F°/17C°

Schedules: . . .

. .

. . . . . . . . . . . .

 

(1) Day and (1) Night (Setback) settings per day (Require Shutdown or Tstat mode)

Night Setback:

. .

. . . . . . . . . . . . .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. .

.

.

.

. .

.

.

.

.

.

. 0F°/0C° to 75F°/42C°

Power Backup:

. .

. . . . . . Lithium coin battery, 100 days minimum 5 year replacement (Maintains Clock in power outages).

External Inputs:

.

. . . . . . . . .Tstat Input/Shutdown Input/Setback Input, and Prove Input/DHW Input (Dry Contacts Only)

Season:

. .

. . . . . . . . . . . .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. .

.

.

.

. .

.

.

.

.

.

. . Winter and Summer.

BMC-6X SPECIFICATIONS

(Each BMC-6X can add up to (6) additional modulating boilers. A maximum of two BMC-6Xs can be added to a single BMC.)

Extension Numbering:

. . . . . . . . . . . . . . . . . . . . . . . .

.

.

.

.

.

.

.

.

.

.

.Toggle Switch A or B

Boiler Outputs:

. . . . . . . . . . . . . . . . . . . . . . . . .

.

. .

.

.

.

.

.

.

. . . (6) N.O. S.P.S.T.

Modulating Output Types:

. . . . . . . . . . . . . . . . . . . . . . . .

 

(6)

4-20mA, 0-5V, 0-10V, 1-5V, 2-10V

Output Relay Ratings:

1 Amp inductive (1/8HP), 6Amp resistive at 120 VAC 60 Hz, 15A total for all circuits

Connection to BMC and another extension:

. . . . . . . . Two RS485 connections using 6 wire phone cable (Cable is provided)

HT #059071-00 A

500 Blaine Street Michigan City, Indiana 46360

219-879-6561 http://www.weil-mclain.com

Part Number 550-100-072/0408

32

Page 32
Image 32
Weil-McLain operation manual BMC Specifications, BMC-6X Specifications