Conair UGH016/0500 manual Replacing Fuses, WARNING Electrical hazard, Remove and replace fuses

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 70
Image 70
REPLACING

REPLACING

FUSES

Always refer to the wiring dia- grams you received with your chiller to locate specific elec- trical components.

WARNING: Electrical hazard

Before performing any work on this unit, discon- nect and lock out electrical power sources to prevent injury from unexpected energization or startup.

To replace fuses:

1

Disconnect and lockout power to the chiller.

 

 

 

 

 

 

 

 

 

 

 

2

Open the electrical enclosure and locate

 

 

the fuses. Refer to the wiring diagram for the exact loca-

 

 

tion.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Remove and replace fuses.

 

 

 

 

 

 

 

 

 

 

 

4

Restore power to the chiller.

 

 

 

 

 

 

 

 

Control transformer

 

 

 

Control transformer

 

 

primary fuses

 

 

 

secondary fuse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6-20TROUBLESHOOTING Series 1 Portable Chillers, TIC Control

UGH016/0500

Page 70
Image 70
Conair UGH016/0500 manual Replacing Fuses, WARNING Electrical hazard, Disconnect and lockout power to the chiller