MECHANICAL CONDITIONS

Look here when the Alarm/Shutdown light on the control panel is lit. See Answering an Alarm, in the Troubleshooting section before going to these tables.

MECHANICAL CONDITIONS

Alarm

Possible cause

Solution

 

 

 

Low Water Tank

Water level in tank is low.

Fill tank to proper level. See

Level (pump and

 

Checking Reservoir Level, in

compressor are off)

 

the Maintenance section.

 

 

Inspect for leaks in the process

 

 

piping. Repair as necessary.

See Making Plumbing Connections, in the Installation section.

Failed Level switch.

Check level gauge and com-

 

pare it to status of the level

 

switch by checking continuity

 

of switch in electrical enclo-

 

sure. Refer to wiring diagrams.

 

 

UGH016/0500

Series 1 Portable Chillers, TIC Control

TROUBLESHOOTING 6-7