1 Prepare a 5% solution of Phosphoric acid

Minerals and other contaminants produce deposits, scales, slime, or algae on the heat transfer surfaces exposed to water. Fouled surfaces result in decreased cooling capacity. Implement a water treatment program to slow the fouling.

CAUTION: Hot Surfaces

Always protect yourself from hot surfaces when working on the Portable Chiller, especially when working on or around the compressor and con- denser. These devices can reach up to 160 °F (71 °C). Allow these devices to cool before per- forming any maintenance or troubleshooting.

Water quality should be maintained at a pH of 7.4, but not less that 6.0 for proper heat exchanger life.

To clean:

1 Prepare a 5% solution of Phosphoric acid

or Oxalic acid. Do not heat the acid solution.

CLEANING THE

EVAPORATOR OR

WATER-COOLED

CONDENSER

2

Shut the From Process valve.

 

 

 

 

 

 

 

3

Disconnect the pump from the heat exchanger.

 

Install a cap in the opening of the heat exchanger where

 

the pump was connected.

 

 

 

 

 

 

 

4

Connect 1/2-inch tubing to the 1/2-inch

 

connections of the heat exchanger.

 

 

 

 

 

 

 

5

Back-flush the solution through the

 

heat exchanger and the chiller.

 

 

 

6

Flush the heat exchanger and the chiller

 

piping with fresh water after cleaning.

 

 

 

7

Reconnect the chiller pump to the

 

heat exchanger. Remove the cap in the heat exchanger

 

and reconnect the hose from the pump.

 

 

 

 

 

 

 

 

 

 

 

 

1/2 inch connection on

 

 

Heat

 

 

Exchanger

 

outside of chiller cabinet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluid circuit

CLEANING THEShut the From Process valve. Acid solution

To Process connection

Out

In

Disconnect the pump from the heat exchanger.the pump was connected. Out

Connect 1/2-inch tubing to the 1/2-inchconnections of the heat exchanger. In

UGH016/0500

Series 1 Portable Chillers, TIC Control

MAINTENANCE 5-7