4 Check the continuity within the switch

4 Check the continuity within the switch

and make sure it corresponds to the following conditions:

Item

Description

 

 

High Pressure Switches (PS-2)

Cut out @ 300 PSIG on rise

Low Pressure Switches (PS-1)

Cut out at 28 PSIG on fall

 

Cut in at 43 PSIG on rise

 

 

If required, check the switch with a refrigeration gauge. If the switch does not change, as listed in this table, when compared to a refrigeration pressure gauge, the switch is faulty. Replace the switch.

CHECKING

PRESSURE

SWITCHES

CONTD

UGH016/0500

Series 1 Portable Chillers, TIC Control TROUBLESHOOTING 6-23