Possible cause Solution

MECHANICAL

CONDITIONS

CONTD

Alarm

Possible cause Solution

Pump Overload Overload set incorrectly. (pump and compres-

sor are off)

Low supply voltage.

Check table on wiring diagram for correct amperage. Adjust overload accordingly.

Check supply voltage. Supply voltage to contactor should be +- 10% of name- plate voltage.

Check wire terminations and connections. Tighten if loose.

Faulty contactor

Check line and load side of

 

contactor. It should be less

 

than 5 volt drop across the

 

contactor. If it is not, replace

 

the contactor. See Replacing

 

the Contactor in the

 

Troubleshooting section.

Faulty overload module.

Check amp draw of circuit. If

 

it is under the rated setting,

 

replace the overload module.

 

See Replacing Overload

 

Modules, in the

 

Troubleshooting section.

 

 

UGH016/0500

Series 1 Portable Chillers, TIC Control

TROUBLESHOOTING 6-9