Conair UGH016/0500 Specifications, 2-10, Model, W1-1.5, W1-2, W1-3, W1-4, W1-5, W1-7.5, W1-10

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 18
Image 18
SPECIFICATIONS

SPECIFICATIONS

Water-cooled Models

front

A

side

F back

D

E

MODEL 10.5 {267}

W1-1.5 5.5 {140}

B

C

10 {254}

9 {229}

 

MODEL

W1-1.5

 

W1-2

 

W1-3

W1-4

W1-5

W1-7.5

W1-10

W1-15

 

Performance characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacitytons

 

1.44

 

1.93

 

3.23

4.44

5.00

7.09

10.22

14.68

 

 

Compressor Hp {kW}

1.5 {1.1}

 

2 {1.5}

 

3 {2.2}

4 {3}

5 {3.7}

7.5 {5.6}

10 {7.5}

15 {11}

 

 

Pump Hp {kW}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 Hz

0.75 {0.6}

 

0.75 {0.6}

 

1 {.8}

1 {.8}

1.5 {1.1}

1.5 {1.1}

1.5

{1.1}

2 {1.5}

 

 

50 Hz

1.5 {1.1}

 

1.5 {1.1}

 

1.5 {1.1}

2 {1.5}

2 {1.5}

2 {1.5}

2 {1.5}

2 {1.5}

 

 

Chilled water flowgpm {lpm}

6.9 {25.1}

 

4.6 {17.4}

 

7.8 {29.5}

10.7 {40.5}

12.0 {45.4}

17.0 {64.3}

24.5

{92.7}

35.2 {133.2}

 

 

Chilled water pressure§ psi {bar}

27.8 {1.9}

 

29.9 {2.1}

 

32.9 {2.3}

31.8 {2.2}

41.6 {2.9}

34.8 {2.4}

29.3 {2.0}

32.3 {2.2}

 

 

Reservoir capacity gal {l}

8.0 {30.3}

 

15 {57}

 

15 {57}

15 {57}

15 {57}

25 {95}

25

{95}

25 {95}

 

 

Condenser water flow gpm {lpm}

5.0 {18.9}

 

6.4 {24.2}

 

10.3 {39.0}

14.2 {53.7}

16.7 {63.2}

24.1 {91.2}

31.7 {120}

45.4 {172}

 

 

Dimensions in {mm}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A-Height

 

49 {1245}

 

 

 

 

49 {1245}

 

 

 

 

 

61 {1549}

 

 

 

 

B-Width

 

34 {864}

 

 

 

 

34 {864}

 

 

 

 

 

34 {864}

 

 

 

 

C-Length

 

39.5 {1003}

 

 

 

 

45.5 {1156}

 

 

 

 

 

55 {1397}

 

 

 

 

D-Height to condenser out

37 {940}

 

38.5 {978}

 

38.5 {978}

38.5 {978}

38 {965}

41.3 {1049}

41.3 {1049

41.3 {1049}

 

 

E-Height to condenser in

31 {787}

 

32.5 {826}

 

32.5 {826}

32.5 {826}

32 {813}

35 {889}

35 {889}

35 {889}

 

 

F-Distance to valve

 

 

 

4 {102}

 

 

 

 

 

 

 

 

4.5 {114}

 

 

 

 

 

 

 

 

Weight lb {kg}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installed

420 {190}

 

585 {265}

 

585 {265}

840 {381}

840 {381}

1080 {490}

1090 {494}

1095 {497}

 

 

Shipped

550 {249}

 

755 {342}

 

755 {342}

1010 {458}

1010 {458}

1250 {567}

1260 {572}

1265 {574}

 

 

Utility requirements

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Process connections NPT in

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

Condenser water NPT in

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

Power consumption amps

run

 

full

 

run

full

 

run

full

run

full

run

full

run

 

full

run

 

full

run

full

 

230V/3 phase/60hz*

9.5

 

15.3

 

10.2

15.6

 

15.1

24.4

18.7

29.4

22.5

36.3

29.2

 

44.7

35.0

 

56.0

44.8

79.0

 

 

220V/3 phase/50hz

13.1

 

19.1

 

13.8

19.4

 

17.8

27.5

22.5

33.6

24.3

38.6

31.3

 

47.4

37.4

 

59.1

46.8

82.1

 

 

460V/3 phase/60hz*

4.5

 

6.9

 

4.9

7.1

 

7.3

11.1

9.1

13.3

10.9

16.4

14.2

 

20.2

17.1

 

25.3

22.0

35.7

 

 

575V/3 phase/60hz*

3.6

 

5.5

 

3.9

5.7

 

5.8

8.9

7.3

10.7

8.7

13.1

11.4

 

16.2

13.7

 

20.2

17.6

28.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPECIFICATION NOTES

Based on 50 °F (10 °C) water temperature (100% water) leaving the chiller, standard pump selections, 85 °F (27 °C) condenser water supply

@ 25 psi minimum, for the 60 Hz units. For the 50 Hz units, multiply the capacity by 0.8 Consult factory for other conditions. Capacity ratings are (+-) 5% based on compressor manufacturer’s ratings and are subject to change without notice.

Based on 50° F (10 °C) water temperature leaving the chiller and 60 °F (16 °C) water temperature returning to the chiller (except W1-1.5 which has 55 °F (13 °C) water temperature returning to the chiller).

§Pressure at pump discharge. See Pressure Tables in the Appendix for Evaporator and Condenser pressure drops. * Optional

2-10

DESCRIPTION Series 1 Portable Chillers, TIC Control

UGH016/0500

Page 18
Image 18
Conair UGH016/0500 Specifications, 2-10, Model, W1-1.5, W1-2, W1-3, W1-4, W1-5, W1-7.5, W1-10, W1-15, Dimensions in mm