WARNING: Electrical hazard

Before performing any work on this unit, discon- nect and lock out electrical power sources to prevent injury from unexpected energization or startup.

Normally if the overload trips, resetting the overload and cor- recting the cause is typically all that is needed. However, if the overload continues to trip, it may be necessary to replace the overload module.

To replace the overload module:

1 Disconnect and lockout power to the chiller.

2

Open the electrical enclosure.

 

 

3

Locate the overload module and disconnect

the power leads from the module to the device. Refer to the wiring diagram for the exact location. Note the place- ment of each lead and label as needed.

4 Disconnect auxiliary wiring to the module.

5 Loosen the screws and remove the module.

6 Install the new module

and tighten in place with the screws.

7

Reconnect wires and leads.

 

 

8

Adjust setting to correct Full Load Amps

 

rating of compressor, fan or pump.

 

 

9

Restore power to the chiller.

Pump overload

module

Compressor over-

load module

REPLACING

OVERLOAD

MODULES

Always refer to the wiring dia- grams you received with your chiller to locate specific elec- trical components.

UGH016/0500

Series 1 Portable Chillers, TIC Control TROUBLESHOOTING 6-19