Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 53
Image 53
IDENTIFYING

The Troubleshooting section covers problems directly related to the operation and maintenance of the portable chiller. This section does not provide solutions to problems that originate with other equipment. Additional troubleshooting help can be found in manual supplied with the other equipment.

Conditions you may see are:

electrical - a fuse is out, a switch has tripped

mechanical - pump, condenser not working

physical - water flow incorrect

As part of troubleshooting you need to know the status of the inputs and outputs. Open the electrical enclosure and check the status of the inputs and outputs. When they are in normal range, the numbers are highlighted. If the number is not high- lighted, it is out of range.

IDENTIFYING

THE CAUSE OF

A PROBLEM

Always refer to the wiring diagrams you received with your chiller to locate specific electrical compo- nents.

Inputs

Outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

1

2

3

4

5

6

7

 

8

9

10 11 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DAY

 

 

 

 

 

TIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

1

 

 

2

 

3

4

5

 

6

7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this example, inputs 7 and 8 are highlighted; they are in normal position. The unhighlighted numbers are out of range.

Refer to the wiring diagram and the following table for the switch status:

Input

Description

Output Description

1

Chiller Stop

1

Compressor Starter

2

Chiller Start

2

Compressor Run Lamp

3

Level Switch

3

Pump Starter

4

Flow Switch

4

Pump Run Lamp

5

Compressor Running

5

Alarm Lamp

6

Pump Running

6

Optional Auto-Fill Solenoid

7

Suction Pressure Switch

7

Optional Alarm Bell

8

Discharge Pressure Switch

8

Optional Alarm Strobe

9

Low Temperature Deviation

 

 

 

10

Optional Auto-Fill Level Switch

 

 

11

Pressure Differential Switch

 

 

 

(7.5, 10, 15 ton only)

 

 

12

Optional Alarm Silence

 

 

 

 

 

 

UGH016/0500

Series 1 Portable Chillers, TIC Control

TROUBLESHOOTING 6-3

Page 53
Image 53
Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control, UGH016/0500 manual Time