Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 61
Image 61
Clogged/dirty air-cooled

MECHANICAL

CONDITIONS

CONTD

Alarm

Possible cause

Solution

 

 

 

High Discharge Pressure (pump is running, compressor is off)

Clogged/dirty air-cooled

Clean the coil. See Cleaning

condenser.

the Air-cooled Condenser, in

 

the Maintenance section.

Blocked air flow to air-
Move chiller or unblock air
cooled condenser.
passageway.

 

 

Low condenser water
Check required flow; see
flow or water too warm
Specifications in the
to water-cooled con-
Description section.
denser.

 

Blocked condenser water Unblock line; open valve. line or valve closed.

Water-cooled condenser fouled.

Clean the condenser. See Cleaning the Air-cooled Condenser, and Cleaning the Evaporator or Water-cooled Condenser, in the Maintenance section.

UGH016/0500

Series 1 Portable Chillers, TIC Control TROUBLESHOOTING 6-11

Page 61
Image 61
Conair Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control Mechanical Conditions, Alarm