Conair UGH016/0500 Mechanical Conditions, Alarm, Possible cause, Solution, Pump is not running

Models: UGH016/0500 Portable Chillers Series 1Water-Cooled (W1) and Air-Cooled Models (A1) withTIC Control

1 88
Download 88 pages 7.31 Kb
Page 58
Image 58
The To Process and From Open valve(s).

MECHANICAL

CONDITIONS

Alarm

Possible cause

Solution

 

 

 

Flow fault (pump and compressor are off)

The To Process and From Open valve(s).

Process valves are closed.

The Process Fluid strain- Clean the strainer. er is clogged.

Water level in reservoir is

Fill the reservoir. See Making

low.

Process Plumbing

 

Connections, in the Installation

 

section.

The evaporator is fouled. Clean Evaporator. See Cleaning the Evaporator or Water-cooled Condenser, in the Maintenance section.

Pump is not running.

Check overload module.

 

Replace as needed. See

 

Replacing Overload Modules,

 

in the Troubleshooting section.

 

Pump is running back-

Switch any two of the three

 

 

wards.

main power leads to the pump.

 

 

 

 

 

 

 

 

 

6-8

TROUBLESHOOTING Series 1 Portable Chillers, TIC Control

UGH016/0500

Page 58
Image 58
Conair UGH016/0500 Mechanical Conditions, Alarm, Possible cause, Solution, The To Process and From Open valves, wards