In some installations, the alarm output is$GYDQFHGused to activate7HFKQRORJ\or deactivate9LGHR,QFhighvoltage and/or high current circuitry (110 VAC lights, siren, etc.) which cannot be controlled directly by the
The easiest method to address the above cases is to use a relay, which has the number and rating on its contacts sufficient for the alarm output. Shown below are two methods to control a high current or high voltage device using a relay with a single, normally open contact. An internal, current limiting resistor for the pin 9 +5V supply will limit the usable relay current to something less than 10 mA (depending on the coil impedance). If a higher voltage or higher current relay is used, an external supply is required. Under these conditions the open circuit voltage (no alarm) on pin 9 must not exceed 30 VDC and the closed circuit current (alarm active) into pin 9 must be less than 50 mA.
The breakout adapter board is numbered compatibly with the
Note: Pin 16 is only present on the Breakout Adapter and is connected to chassis ground.
High Current/Voltage Alarm Output
To be used when output current exceeds 50 mA or when,
1
| CLOSED = Alarm activated | ||
9 | OPEN | = No alarm | |
| - |
|
|
| 5 VDC Relay |
| |
| Less than 10 mA | ||
16 | + |
|
|
1 |
|
|
|
| CLOSED = No alarm | ||
| OPEN | = Alarm activated | |
9 | Vout |
|
|
CLOSED = Alarm activated | |||
| OPEN | = No alarm | |
| Vout | Relay |
|
16 | +30 VDC, 50 mA max. | ||
|
ALARM CONNECTOR PINS
1 | Alarm1 | 9 | Alarm Out (< 50 mA) |
2 | Alarm2 | 10 | Freeze/Master Enable |
3 | Alarm3 | 11 | (reserved for future use) |
4 | Alarm4 | 12 | (reserved for future use) |
5 | NA | 13 | +5V ( < 10 mA) |
6 | NA | 14 | (reserved for future use) |
7 | NA | 15 | Signal ground (< 10 mA) |
8 | NA | 16 | Chassis ground |
| Page 19 |