Liebert 130 kVA user manual Display Panel Messages, Sr. No Display Message Alarm Interpretation

Models: 130 kVA

1 102
Download 102 pages 29.34 Kb
Page 77
Image 77

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

7.2Display Panel Messages

The message displayed on Hipulse can be categorized into types:-

(a)ALARM messages - these are messages which needed urgent attention and warn of a UPS shutdown or imminent shutdown the load would normally transfer to the bypass supply if it is available. All alarm messages are accompanied by an audible warning.

(b)WARNING messages - these are the messages generated to warn or confirm to the operator of action taken (i.e. if the rectifier a.c. input supply power switch was opened the Warning message would read RECTIF. SWITCH OPEN).

The following table lists the various messages displayed on the operator panel together with a description of their interpretation.

Sr. No.

Display Message Alarm

Interpretation

1.

EMERGENCY STOP

This alarm indicates that the UPS was shut down by means of the

 

 

local or remote (if fitted) Emergency Power Off push button (EPO)

 

 

which is normally due to operation action – investigate the cause

 

 

for pressing the button. If this button was not pressed then check

 

 

the continuity of the circuit to the Remote switch, Customer

 

 

connections, Auxiliary terminal block X4; pin 5 and 6; normally

 

 

closed.

2.

INV. OFF

The INV. OFF alarm is active whenever the inverter is not producing

 

 

its correct output voltage, either because it has been switched OFF

 

 

or due to an internal fault, it will normally be accompanied by one

 

 

or more of the other inverter fault conditions.

 

 

 

3.

INV: OVERVOLTAGE

Most of the inverter fault messages are self explanatory, however

 

INV: UNDERVOLTAGE

the WAVEFORM ERR informs the operator that the output voltage

 

OUTPUT: NO VOLTAGE

peak has flattened caused by an internal inverter problem and

 

OUTPUT: WAVEFORM ERR

therefore the output will be out of limits.

 

 

 

4.

INV. OVERTEMPER.

Over temperature is sensed by a normally-closed thermostat (90°C

 

 

operating) fitted to each inverter heat sink. If an over temperature

 

 

condition arises, the audible alarm will accompany this message;

 

 

the inverter stops and load transfers to Bypass after 3 minutes.

 

 

 

5.

OVERTEMP. SHUTDOWN

This message informs the operator that the inverter has been

 

 

switched OFF and that the load has been transferred ot Bypass due

 

 

to an Inverter over temperature.

6.

OVERLOAD PRESENT

The inverter overload has an inverse load/ time characteristic – i.e.

 

 

it will accept 125% overload for 10 minutes and 150% overload for

60 seconds. If this characteristic is exceeded the load transfers to the bypass supply, the inverter stops and the overload alarm annunciates. The [OVERLOAD PRESENT] alarm will annunciate as soon as the load exceeds 100% of the UPS rating, and the load will transfer to Bypass some time later, depending on the degree of

57