22.

BATTERY ON LOAD

This is a status warning that the battery is discharging. It normally

 

 

accompanies a [BYP: ABSENT] or [RECT: OFF] message.

23.

AUTONOMY XXXX min

The micro monitors the battery percentage capacity while on charge

 

 

and the battery time remaining while on discharge. It calculates the

 

 

time remaining as function of the discharge current against the

 

 

programmed ampere-hour capacity of the battery. It will update the

 

 

time remaining as the load is change.

 

 

 

24.

BATTERY UNDER TEST

This message informs the operator that the system is carrying out a

 

 

periodic battery test.

25.

BOOST TIME EXPIRED

This message is only applicable to systems which include the boost

 

 

charge option, boost time charge elapsed set value, battery should

 

 

be controlled by service personnel.

26.

LOAD ON BYPASS

This is a status warning that the load is being powered through the

 

 

static bypass line and is unprotected from mains supply

 

 

aberrations.

 

 

This action is either selected by the operator or a fault condition,

 

 

check for other fault messages.

 

 

 

27.

RECT: OFF

This is a status message confirming that the rectifier has been

 

RECT: OFF VIA DISPLAY

selected off by the operator from either the front panel display or an

 

 

external PC or by a switch on UPS microprocessor PCB.

28.

BYP: OFF

This is a status message confirming that the bypass has been

 

BYP: OFF VIA DISPLAY

inhibited by the operator from either an external PC or by a switch

 

 

on UPS microprocessor PCB.

29.

INV: OFF

This is a status message confirming that the inverter has been

 

INV: OFF VIA DISPLAY

selected off by the operator from either the front panel display or an

 

 

external PC or by a switch on UPS micro controller PCB.

 

 

 