Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
9.6UPS Electrical Characteristics (Inverter Output)
|
| I N V E R T E R O U T P U T |
|
|
|
Rated Power | kVA | 130 |
|
|
|
Rated mains voltage j | Vac | 380 - 400 - 415 |
|
| |
|
| Three phase with neutral |
Frequency k | Hz | 50 to 60 |
|
| |
|
|
|
Rated Power at cosφ = 0.8 | KVA | 130 |
|
|
|
Rated Power at cosφ = 1 | KW | 104 |
|
|
|
Overload | % | 150% FOR 60 sec |
|
| 125% for 10 min |
|
| 110% for 1 hr |
Maximum non linear load | - |
|
allowed l |
| 100% Pn |
|
|
|
Voltage stability, steady state test | % |
|
m |
| ± 1.5 |
|
|
|
Voltage stability, transient test n | % | ± 5 |
|
| |
|
|
|
Maximum rate of change of | Hz |
|
frequency o | /sec | 0.1 |
|
|
|
Note:
j= Factory set 400V – 380V or 415V voltages with software setting k = Factory set at 50Hz ; 60Hz with software setting.
l = EN50091-3 (1.4.58) crest factor 3. m = EN50091-3 (4.3.4).
n =
74