At this point the UPS inverter stops but the load

 

 

continues to be supplied by the bypass mains.

 

 

The Load on Mains indicator light (6) on the unit's

 

 

synoptic panel flashes yellow, and the Load on

 

 

Inverter indicator light (5) goes off.

 

 

 

 

 

Your load is now powered via the Static Bypass system

 

 

 

 

 

5. Unfasten the lock, release the internal safety bar

 

 

and close the maintenance bypass power switch

 

 

Q3. Open the Rectifier input power switch Q1, the

 

 

Output power switch Q4, the bypass power switch

 

 

Q2 and the Battery circuit breaker. This is located

 

 

inside the battery cabinet (if used) or is otherwise

 

 

located adjacent to the battery racks. The unit will

 

 

power down but the load will continue to be

 

 

supplied by the manual bypass.

 

 

 

 

 

WARNING

 

 

 

 

 

Wait 5 minutes for the internal D.C. busbar capacitors

 

 

to discharge.

 

 

 

 

WARNING

The following points will be live within the UPS:

-Bypass a.c. input supply terminals.

-Maintenance Bypass power switch.

-Static Bypass power switch.

-UPS output terminals.

Input and Output terminals remain protected by a metallic cover.

Your load is now powered from the maintenance bypass

system and the UPS is completely shut down.