WARNING
Wait 5 minutes for the internal D.C. busbar capacitors to discharge.
The UPS is now completely powered down.
IMPORTANT
The Maintenance Bypass Power switch may be operated at any time when the UPS is powered down to connect the load to the maintenance bypass supply if required.
The load equipment is not protected from normal supply aberrations when operating in the maintenance bypass mode.
5.7Procedure for carrying out a RESET after a recognized controlled transfer to bypass or EPO action.
When the necessary action to correct the problem has been taken, this procedure should be followed to restore the UPS back to its normal operating condition following, a controlled transfer to bypass or when the Remote Emergency Power Off has been activated.
A recognized controlled transfer to bypass is activated by the following problems: Inverter Overtemperature,
EMERGENCY STOP
LOAD ON BYPASS INV: UNSYNCHRONISED
hh.mm.ss dd.mm.yy
MEASUREMENT
>FUNCTION<
MAINTENANCE SETUP
−WRITE | SAVE ↵ |
↓MOVE | EXIT ESC |
ENTER PASSWORD 00000000
Press the ENTER key.
Note: In ECOMODE the message 'LOAD ON BYPASS' will not appear.
Select FUNCTION and press ENTER key.
When the PASSWORD has been completed press ENTER key.
39