Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
Chapter 9
Specification
This specification describe requirements for an Uninterruptible Power System (UPS).
9.1Conformity and Standard
The UPS has been designed to conform the following standards: IEC, EN
9.2UPS Environmental
The UPS shall be able to operate under the following environmental conditions without damage or degradation in electrical operating characteristics:
Environmental Characteristics | Units |
|
Rated Power | kVA | 130 |
Operating Temperature | ºC | 0 to 45 ºC |
Relative Humidity | % | = 90% at 31 ºC, Saliferrous, Humid |
Altitude of operation | m | = 1000m above sea level |
Storage/ transport temperature | ºC | |
|
|
|
9.3UPS Mechanical Characteristics
Mechanical | Units | 130 kVA |
Characteristics |
| 6 pulse |
Height | mm | 1900 |
Width | mm | 1400 |
Depth | mm | 925 |
Ventilation | - | By internal intake fans |
Cable entry | - | Bottom |
Protection | IP | 41 |