Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

5.12 Language Selection :

If required, select the appropriate language using the following procedure.

MEASUREMENT

>FUNCTION<

MAINTENANCE SETUP

WRITE

SAVE

MOVE

EXIT ESC

ENTER PASSWORD

00000000

BATTERY TEST

 

GENERATOR

 

 

>PANEL SETUP

 

<

NEXT PAGE

 

 

 

 

 

 

 

 

>LANGUAGE

ENG

<

TYPE 0000

MASTER

 

GROUP 1

UPS 1

 

PASSWORD 00000000

From ‘Default’ window, press ENTER key.

Select the FUNCTION and press the enter key.

A password must be entered to gain a further access to next menu. The initial default password of ‘00000000’ need not be changed at this point of time. Press the enter key.

Select PANEL SET UP and press enter key.

Select LANGUAGE and press the ENTER key.

Use the UP push button to rotate through the available options and select the required default language. The options are: English, Italian, German, French , Dutch & Spanish.

Press ENTER to accept and store the language selection, then step back to the default window by repeatedly pressing ESC as required; the current alarms should now be stored in the selected language.

Note: Ensure the data entered during the following procedures are r3cordded in the appropriate commissioning documentation.

5.13 Changing the current Date and Time

1.From DEFAULT WINDOW, pressing ENTER key, select MAINTENANCE >> ENTER>> PASSWORD>> ENTER>> select and enter the line showing the time and date.

2.Position the cursor on the row on which the date-time is displayed, and press

ENTER.

3.Using the 'UP' and 'DOWN' menu buttons, enter the current time and date information.

4.Press ENTER to save the settings, then press ESC twice to return to the DEFAULT WINDOW.

45