Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

9.5UPS Electrical Characteristics (DC Intermediate Circuit)

D. C. I N T E R M E D I A T E C I R C U I T

Rated Power

kVA

130

 

 

 

Voltage range for Inverter operation

Vdc

340 – 480

 

 

 

Recommended number of

Nos.

190 (380 Vac)

-

Lead-acid cells j-k

 

198 (400 Vac)

 

 

 

204 (415 Vac)

-

Ni-Cd cells j-k

 

320 (454.4 Vac)

Recommended float charge voltage

Vdc

432 (380 Vac)

2.25 V/cell (Lead Acid) j

 

446 (400 Vac)

 

 

 

459 (415 Vac)

1.42 V/cell (Ni-Cd) j

 

454.4 Vac

Recommended boost charge voltage

Vdc

460 (380 Vac)

2.40 V/cell (Lead Acid) j

 

475 (400 Vac)

 

 

 

490 (415 Vac)

1.55 V/cell (Ni-Cd) j

 

480 Vac

Recommended end of discharge voltage

Vdc

320 (380 Vac)

1.67 V/cell (Lead Acid) j

 

330 (400 Vac)

 

 

 

340 (415 Vac)

1.1 V/cell (Ni-Cd) j

 

340 Vac

Recommended test voltage

Vdc

365 (380 Vac)

for Lead Acid j

 

376 (400 Vac)

 

 

 

388 (415 Vac)

for Ni-Cd j

 

384 Vac

Battery boost charge cycle l

-

Characteristics to DIN 41772I-U, boost to floating charge

 

 

 

switching, with current measuring criterion plus control of

 

 

 

charging time.

Maximum boost charge duration l

min

0-999

 

 

 

 

 

 

Boost-float threshold current l

A

0-99

 

 

 

 

 

 

Ripple voltage superimposed m

%

 

 

 

 

2

 

 

 

 

Note:

j= (According to rated voltage)

k= Factory set for rated 400V, different cells number and voltage per cell may be set by software and / or trimmers on Rectifier control board.

l= Set by software

m= Battery disconnected, RMS percentage value referred to DC voltage.