User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

9.4UPS Electrical Characteristics

 

 

R E C T I F I E R I N P U T M A I N S

 

 

 

I/P Ratings

Units

130 kVA

 

 

6 pulse

Rated power

kVA

130

Rated Mains

Vac

380 – 400 – 415 V

Voltage j

 

 

Supply

 

Three phase without neutral

 

 

 

Input voltage

%

±10

tolerance k

 

 

Frequency

Hz

50 or 60

 

 

 

Input

%

± 5

frequency tol.

 

 

Rated input

kVA

143

power l

 

 

Rated input

A

206.4

current l

 

 

Maximum

kVA

178

input power

 

 

m

 

 

Maximum

A

257

input current

 

 

m

 

 

Duration of

sec

 

progressive

 

2 to 10

power walk-in

 

 

n

 

 

j= 380V or 415V set changing taps on auxiliary supply transformer

k= With mains at –15% and suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge.

l= EN 50091-3 (1.4.39): UPS, rated load, input rated voltage 400V, no current to battery

m= EN 50091-3 (1.4.40): UPS, rated load or overload, input rated voltage 400V, battery on boost charge with maximum allowed current.

n= Set with jumper on Rectifier control board.