Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
9.4UPS Electrical Characteristics
|
| R E C T I F I E R I N P U T M A I N S |
|
|
|
I/P Ratings | Units | 130 kVA |
|
| 6 pulse |
Rated power | kVA | 130 |
Rated Mains | Vac | 380 – 400 – 415 V |
Voltage j |
|
|
Supply |
| Three phase without neutral |
|
|
|
Input voltage | % | ±10 |
tolerance k |
|
|
Frequency | Hz | 50 or 60 |
|
|
|
Input | % | ± 5 |
frequency tol. |
|
|
Rated input | kVA | 143 |
power l |
|
|
Rated input | A | 206.4 |
current l |
|
|
Maximum | kVA | 178 |
input power |
|
|
m |
|
|
Maximum | A | 257 |
input current |
|
|
m |
|
|
Duration of | sec |
|
progressive |
| 2 to 10 |
power |
|
|
n |
|
|
j= 380V or 415V set changing taps on auxiliary supply transformer
k= With mains at
l= EN
m= EN
n= Set with jumper on Rectifier control board.
72