Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

overload present.

7.

OVERLOAD SHUTDOWN

This message informs the operator that the load has been

 

 

transferred to bypass due to an inverter overload.

 

 

 

8.

OUTPUT SWITCH OPEN

This is a status alarm. The output switch must be selected

 

 

‘CLOSED’ at all times except when operating on the Maintenance

 

 

bypass supply.

 

 

 

9.

BYPASS SWITCH OPEN

This is a status alarm. The bypass input switch must be closed all

 

 

the times.

 

 

 

10.

BATTERY C.B. OPEN

This is a status indication only. Note that if the UPS is operating

 

 

with the Battery circuit breaker open, and the mains power fails,

 

 

then the UPS output will also fail together with load power, since

 

 

the inverter has no battery backup.

 

 

 

11.

BATTERY: FUSE FAIL

This problem should be rectified as soon as possible. If the mains

 

 

power fails then the UPS output will also fail together with load

 

 

power, since there is no battery backup.

 

 

 

12.

BATTERY: TEST FAILED

The system has carried out a test of the battery. If this alarm is not

 

 

accompanied by a [BATTERY C.B. OPEN] or [BATTERY: FUSE FAIL]

 

 

message then a full check of the Battery bank is required.

 

 

 

13.

DC BUS: UNDERVOLTAGE

When the inverter is operating on the battery this message is

 

 

displayed on the condition when battery voltage has fallen below a

 

 

preset value. If the input a.c. power cannot be restored, you should

 

 

shut down your loads.

 

 

 