Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

9.7UPS Electrical Characteristics (Bypass Input Mains)

 

 

B Y P A S S I N P U T M A I N S

 

 

 

Rated Power

kVA

130

 

 

 

Rated mains voltage j

Vac

380 - 400 - 415

 

 

 

 

 

Supply

 

Three phase with neutral

 

 

 

Rated Current:

A

1182

110 Vac

 

 

 

 

 

Bypass voltage tolerance k

%

± 10

 

 

 

Delay time to recognize bypass

sec

10

voltage returned to window

 

 

Inverter output voltage window

%

± 10

 

 

 

Frequency l

Hz

50 or 60

 

 

 

Input frequency tolerance m

%

± 2

 

 

 

 

 

Maximum frequency slew rate

Hz

 

 

/sec

0.1

 

 

 

Current rating of neutral cable

 

1.5 x In

 

 

 

 

 

Protection, bypass line

 

To avoid series fuses, the bypass line should be protected using an

 

 

external device should be sized to discriminate with the load

 

 

protection.

Overload

%

150% for 60 sec

 

 

125% for 10 min

 

 

110% for 1 hr

Note:

j= Factory set 400V – 380V or 415V set changing taps on auxiliary supply transformer and with software setting k = Other values 0-15% with software setting.

l = Factory set at 50Hz ; 60Hz with software setting. m = Other values 1-9% with software setting.