Select MEASUREMENT and press ENTER key.

Select BATTERY and d.c. busbar voltage will be displayed:

BATTERY

 

 

VOLTAGE

446

[V]

CURRENT

001

[A]

CHARGE

000

[%]

 

 

 

If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system, 446VV d.c. for 400V a.c. system and 459V d.c. for a 415V a.c. system) press the Escape key repeatedly until the display returns to the original window.

6.Manually close the battery circuit breaker. This is located inside the battery cabinet (if used) or is otherwise located adjacent to the battery racks.

The Module Mimic indicator (3) Battery unavailable should extinguish. Several LED’s on the Battery state of charge bargraph (17) will illuminate showing the battery state of charge

When the battery circuit breaker has been closed and the inverter has stabilized the screen will change to the default window.

NORMAL OPERATION

hh.mm.ss dd.mm.yy

Default window:

The message shown below, will be seen on the default screen whenever the UPS is operating normally:

The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.

NORMAL OPERATION (ECOMODE)

hh.mm.ss dd.mm.yy

The UPS is operating normally with its

Inverter supplying the load.

ECOMODE:

The following message will appear in the default screen whenever the UPS is operating in ECOMODE. The load is supplied through Bypass Mains.

The UPS is operating in ECOMODE with the Bypass

Mains supplying the load.