Liebert 130 kVA user manual Battery temperature Board

Models: 130 kVA

1 102
Download 102 pages 29.34 Kb
Page 74
Image 74

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

6.10 Battery temperature Board

A battery / sensor card supplied separately from the battery circuit breaker is connected with the UPS logic through the battery circuit breaker card.

With this feature fitted, the nominal float voltage supplied to the battery is adjusted so as to be inversely proportional to the ambient battery cabinet /room temperature. This prevents the battery being over charged at high ambient.

54

Page 74
Image 74
Liebert 130 kVA user manual Battery temperature Board